Article 31
Decree 45/2001/NĐ-CP — Về hoạt động điện lực và sử dụng điện.
The sellers must ensure the quality of electricity supplied to the buyers according to the following regulations:
1. Regarding the voltage:
Under normal conditions, the voltage may fluctuate within ’5% compared to the designated voltage and determined at the secondary side of the transformer supplying electricity to the buyer or at other positions agreed upon by the two parties in the contract when the buyer reaches the capacity coefficient (cos j ) of ’ 0.85 and comply with the additional charge diagram agreed upon in the contract.
In cases where the electricity grids are unstable, the voltage may fluctuate between + 5% and - 10%.
2. Regarding the frequency: Under normal conditions, the electric system frequency may fluctuate within the limit of ’0.2 Hz as compared to the prescribed standard of 50Hz. In cases where the electric systems are unstable, the permitted frequency fluctuation shall be ’0.5Hz.
3. Where the buyer needs electricity with quality higher than the standards prescribed in Clauses 1 and 2 of this Article, the parties must reach agreement thereon in the contract.
Article 31, Decree 45/2001/NĐ-CP