Article 3. Technical standards of electric fences
Decision 07/2006/QĐ-BCN — Về việc quy định tiêu chuẩn kỹ thuật và điều kiện sử dụng điện làm phương tiện bảo vệ trực tiếp
1. Electric fences must be safely designed and installed so as to avoid all accidental contacts with people and cattle, not to affect the normal operation of the electric system, not to cause danger to the vicinity and living environment, to stand the stormy weather and ensure a fine appearance.
2. Electric fences, installed either in combination with other protection fences or isolatedly, must satisfy the following conditions:
a/ Electric fences installed in combination with other protection fences must be put up above other fences with electricity-conducting objects hung at least 2.5 meters above the ground.
b/ For electric fences installed isolatedly, protection fences must be erected inside and outside electric fences so as to prevent accidental contacts between people or animals and electric fences. The distance between electric fences and protection fences shall not be less than 2 meters.
3. Along both sides of an electric fence, there must be signboards reading "Stop! Electricity, fatal danger" put up at noticeable places. The distance between two signboards shall not exceed 20 meters. Signboards shall be hung fixedly 1.7-2 meters above the ground. The design of signboards shall comply with Vietnam standard TCVN 2572-78.
Notes: A signboard shall be 360x240 mm2 in size. Its background is in white, the letters are in black; the frame and voltage signal are in bright red.
4. Voltage used for electric fences is specified as follows:
a/ Below 1,000 V, in cases of using alternating current electric sources;
b/ Unspecified, in cases of using direct current electric sources.
5. At the working places of persons on watch, there must be sound and light alarm systems. Alarm systems must be set off when power failure occurs at electric fences, the electric current is earthed or short-circuited. Alarm signals can be switched off only by persons on watch. The operation of alarm systems shall be checked by pressing testing buttons when the watch work is handed over between two teams of guards.
6. Electricity-conducting objects must meet the following criteria:
a/ Electricity-conducting objects used for electric fences may be metal plates, nets, wires or bars. If steel-plated wires or steel nets are used, their cross-section shall not be less than 6 mm2. Where copper wires or aluminum wires are used, their cross-section shall not be less than 10 mm2. There must be no joint in single conducting wires between two supports so as to ensure mechanical durability. Where it is necessary to conjoin two wires, the ends of these two wires shall be first fixedly tied round a porcelain insulator by a clamp, and twisted or welded together.
b/ Electricity-conducting objects must be fitted firmly and fixedly on porcelain insulators. The distance between two porcelain insulators supporting an electricity-conducting object shall not exceed 5 meters. The distance between two electricity-conducting objects of two adjacent phases or between a phase and the ground shall not exceed 0.2 meter.
c/ Ordinary porcelain insulators shall be placed at an angle of no more than 45o vertically so as to prevent electric leakage caused by rainwater. Where it is necessary to place insulators at an angle exceeding 45o, reinforced porcelain insulators must be used.
Article 3, Decision 07/2006/QĐ-BCN