Article 7. Underground or underwater power cable safety corridors
Decree 106/2005/NĐ-CP — Quy định chi tiết và hướng dẫn thi hành một số điều của Luật Điện lực về bảo vệ an toàn công trình lưới điện cao áp
The underground or underwater power cable safety corridor is delimited as follows:
1. Its length is calculated from the position where the cable runs out of the protection scope of a station to the position where the cable gets into the protection scope of the next station.
2. Its width is delimited by:
a/ Outer side of the cable trough for cables placed in troughs;
b/ Two vertical planes on both sides of the underground or underwater cable line and separated from the outer edge of the cable casing or the outermost cable by distances specified in the following table:
Type of electric cable
Placed directly underground
Placed directly underwater
Stable ground
Unstable ground
Without boat/ship navigation
With boat/ship navigation
Distance
1.0 m
1.5 m
20.0 m
100.0 m
3. Its height is calculated from ground surface or water surface to:
a/ Outer edge of the cable trough base bottom, for cables placed in troughs;
b/ The depth lower than the lowest point of the cable casing by 1.5 m, for cables placed directly underground or underwater.
Article 7, Decree 106/2005/NĐ-CP