Article 4. Safety corridors of overhead power transmission lines
Decree 106/2005/NĐ-CP — Quy định chi tiết và hướng dẫn thi hành một số điều của Luật Điện lực về bảo vệ an toàn công trình lưới điện cao áp
1. The safety corridor of an overhead power transmission line means the space along the line and is delimited as follows:
a/ The length of the corridor is calculated from the position at which the line stretches from the protection boundary of a station to the position at which the line runs through the protection boundary of the next station.
b/ The width of the corridor is delimited by two vertical planes on both sides of the line, running in parallel with the line and with a distance from the outmost wire to each side when the wire in the static state, being specified in the following table:
Voltage
Up to 22 kV
35 kV
66-110 kV
220 kV
500 kV
Insulated wire
Bare wire
Insulated wire
Bare wire
Bare wire
Distance
1.0 m
2.0 m
1.5 m
3.0 m
4.0 m
6.0 m
7.0 m
c/ The height of the corridor is calculated from the bottom of the post base to the highest point of the work plus a vertical safety distance specified in the following table:
Voltage
Up to 35 kV
66-110 kV
220 kV
500 kV
Distance
2.0 m
3.0 m
4.0 m
6.0 m
2. Safety corridors of various power cable lines stretching on the ground surface or hung in the air mean the spaces along such power cable lines and are delimited by a distance of 0.5 m to all sides from the outmost cable.
Article 4, Decree 106/2005/NĐ-CP